Rechenwerk
hydraulic balance
Each radiator output follows Q = Q_N x (dT_ln / dT_ln,N)^n with the logarithmic mean temperature difference dT_ln = (t_v - t_r) / ln((t_v - t_i) / (t_r - t_i)) and the caller’s rating point (default 75/65/20 °C) and exponent. Mode lowest_supply finds the lowest flow temperature at which every radiator covers its room heat load with at least the minimum spread; mode fixed_supply uses the given flow temperature. Per radiator the return temperature is solved by bisection and the mass flow is m.
POST https://rechen.halowerk.com/v1/hydraulic-balanceInputs
| Field | Type | Required | Description |
|---|---|---|---|
| mode | string | No | lowest_supply = find the lowest flow temperature covering all rooms; fixed_supply = use supply_temperature_c. |
| supply_temperature_c | number | No | System flow temperature for mode fixed_supply (°C). |
| min_spread_k | number | No | Minimum temperature spread of the critical radiator in mode lowest_supply (K). |
| radiators | array | Yes |
Show full input schema
{
"type": "object",
"additionalProperties": false,
"required": [
"radiators"
],
"properties": {
"mode": {
"type": "string",
"enum": [
"lowest_supply",
"fixed_supply"
],
"default": "lowest_supply",
"description": "lowest_supply = find the lowest flow temperature covering all rooms; fixed_supply = use supply_temperature_c."
},
"supply_temperature_c": {
"type": "number",
"minimum": 25,
"maximum": 110,
"description": "System flow temperature for mode fixed_supply (°C)."
},
"min_spread_k": {
"type": "number",
"minimum": 1,
"maximum": 40,
"default": 5,
"description": "Minimum temperature spread of the critical radiator in mode lowest_supply (K)."
},
"radiators": {
"type": "array",
"minItems": 1,
"maxItems": 200,
"items": {
"type": "object",
"additionalProperties": false,
"required": [
"id",
"room_heat_load_w",
"rated_output_w"
],
"properties": {
"id": {
"type": "string",
"minLength": 1,
"maxLength": 60,
"description": "Radiator or room label."
},
"room_heat_load_w": {
"type": "number",
"exclusiveMinimum": 0,
"maximum": 100000,
"description": "Design heat load the radiator must cover (W)."
},
"rated_output_w": {
"type": "number",
"exclusiveMinimum": 0,
"maximum": 100000,
"description": "Rated output from the data sheet at the rating point (W)."
},
"rated_supply_c": {
"type": "number",
"minimum": 30,
"maximum": 110,
"default": 75
},
"rated_return_c": {
"type": "number",
"minimum": 25,
"maximum": 105,
"default": 65
},
"rated_room_c": {
"type": "number",
"minimum": 5,
"maximum": 30,
"default": 20
},
"exponent": {
"type": "number",
"minimum": 1,
"maximum": 2,
"default": 1.3,
"description": "Radiator exponent n from the data sheet (panel radiators typically about 1.3)."
},
"room_temperature_c": {
"type": "number",
"minimum": 5,
"maximum": 30,
"default": 20,
"description": "Design room temperature (°C)."
}
}
}
}
}
}Published input example
{
"radiators": [
{
"id": "living",
"room_heat_load_w": 600,
"rated_output_w": 1000
},
{
"id": "bedroom",
"room_heat_load_w": 600,
"rated_output_w": 1500
}
]
}Result & documentation
Machine-readable documentation of this hub
Source of this page: the published HALOWERK catalog. Updated: 2026-11-17 UTC.
More endpoints in this hub
- Rechenwerk0.003 USDC
ai act risk class
POSThttps://rechen.halowerk.com/v1/ai-act-risk-classEvaluates the caller’s description against Regulation (EU) 2024/1689 as amended by Regulation (EU) 2026/1744: prohibited practices of Art. 5(1)(a)-(h) and the new points (ba) and (bb) (from 2 December 2026); high-risk under Art. 6(1) (safet
- Rechenwerk0.002 USDC
annuity schedule
POSThttps://rechen.halowerk.com/v1/annuity-scheduleMonthly annuity in arrears as used by German banks: rate = loan × (nominal rate + initial repayment rate) / 12, or from a term via A = L·q^n·(q−1)/(q^n−1) with q = 1 + i/12; interest each month = balance × i/12 (30/360), rounded to cents, t
- Rechenwerk0.002 USDC
appeal deadlines
POSThttps://rechen.halowerk.com/v1/appeal-deadlinesCovers only clearly codified periods: Berufung one month and grounds two months (§§ 517, 520(2) ZPO), Revision one and two months (§§ 548, 551(2) ZPO), labour court appeal (§ 66(1) ArbGG), all starting with service of the complete judgment